Representation Of Analog Values In The Voltage Output Ranges - Siemens Simatic S7-1500 Manual

Hide thumbs Also See for Simatic S7-1500:
Table of Contents

Advertisement

Table C- 3
Unipolar output ranges
Value dec.
Output
value in %
32511
117,589
32511
117,589
27649
100,004
27648
100,000
1
0,003617
0
0,000
0
0
* When values > 32511 are specified, the output value is limited to 117.589%.
** When values < 0 are specified, the output value is limited to 0%.
C.2

Representation of analog values in the voltage output ranges

The tables below list the decimal and hexadecimal values (codes) of the possible voltage
output ranges.
Table C- 4
Values
>117.589 %
117.589 %
100 %
75 %
0.003617 %
0 %
-75 %
-100 %
-117.593 %
<-117.593 %
Analog output module AQ 4xU/I ST (6ES7532-5HD00-0AB0)
Manual, 09/2016, A5E03484696-AD
C.2 Representation of analog values in the voltage output ranges
Data word
2
2
2
2
2
2
15
14
13
12
11
10
0
1
1
1
1
1
0
1
1
1
1
1
0
1
1
0
1
1
0
1
1
0
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Voltage output range ±10 V
dec
hex
>32511
>7EFF
32511
7EFF
27649
6C01
27648
6C00
20736
5100
1
1
0
0
-1
FFFF
-20736
AF00
-27648
9400
-27649
93FF
-32512
8100
<-32512
< 8100
2
2
2
2
2
2
9
8
7
6
5
4
1
1
x
x
x
x
1
0
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Voltage output range
±10 V
11.76 V
11.76 V
10 V
7.5 V
361.7 µV
0 V
-361.7 µV
-7.5 V
-10 V
-11.76 V
-11.76 V
Representation of analog values
Range
2
2
2
2
3
2
1
0
x
x
x
x
Maximum output
value*
1
1
1
1
Overshoot range
0
0
0
1
0
0
0
0
Rated range
0
0
0
1
0
0
0
0
0
0
0
0
Minimum output
value**
Range
Maximum output value
Overshoot range
Rated range
Undershoot range
Minimum output value
37