Measurement Ranges Of The Analog Inputs For Voltage And Current (Sb And Em) - Siemens Simatic S7 Series System Manual

Hide thumbs Also See for Simatic S7 Series:
Table of Contents

Advertisement

Technical specifications
A.4 Analog inputs and outputs expansion modules (EMs)
A.4.6

Measurement ranges of the analog inputs for voltage and current (SB and EM)

Table A- 104 Analog input representation for voltage (SB and EM)
System
Decimal
Hexadecimal
32767
7FFF
1
32512
7F00
32511
7EFF
27649
6C01
27648
6C00
20736
5100
1
1
0
0
-1
FFFF
-20736
AF00
-27648
9400
-27649
93FF
-32512
8100
-32513
80FF
-32768
8000
7FFF can be returned for one of the following reasons: overflow (as noted in this table), before valid values are availa-
1
ble(for example immediately upon a power up), or if a wire break is detected.
Table A- 105 Analog input representation for current (SB and EM)
System
Decimal
Hexadecimal
32767
7FFF
32512
7F00
32511
7EFF
27649
6C01
27648
6C00
20736
5100
1
1
0
0
-1
FFFF
-4864
ED00
-4865
ECFF
-32768
8000
624
Voltage Measuring Range
±10 V
±5 V
11.851 V
5.926 V
11.759 V
5.879 V
10 V
5 V
7.5 V
3.75 V
361.7 μV
180.8 μV
0 V
0 V
-7.5 V
-3.75 V
-10 V
-5 V
-11.759 V
-5.879 V
-11.851 V
-5.926 V
0 mA to 20 mA
23.70 mA
23.52 mA
20 mA
15 mA
723.4 nA
0 mA
-3.52 mA
±2.5 V
±1.25 V
2.963 V
1.481 V
2.940 V
1.470 V
2.5 V
1.250 V
1.875 V
0.938 V
90.4 μV
45.2 μV
0 V
0 V
-1.875 V
-0.938 V
-2.5 V
-1.250 V
-2.940 V
-1.470 V
-2.963 V
-1.481 V
Current measuring range
4 mA to 20 mA
22.96 mA
22.81 mA
20 mA
16 mA
4 mA + 578.7 nA
4 mA
1.185 mA
System Manual, 09/2015, A5E03822230-AC
Overflow
Overshoot range
Rated range
Undershoot range
Underflow
Overflow
Overshoot range
Nominal range
Undershoot range
Underflow
S7-200 SMART

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s7-200 smart series

Table of Contents