Environmental
NOTE:
Applies to data center environments only. Air
filtration requirements do not apply to IT equipment
designed to be used outside a data center, in
environments such as an office or factory floor.
Conductive Dust
NOTE:
Applies to data center and non-data center
environments.
Corrosive Dust
NOTE:
Applies to data center and non-data center
environments.
Gaseous Contamination
NOTE:
Maximum corrosive contaminant levels measured at ≤50% relative humidity.
Copper Coupon Corrosion Rate
Silver Coupon Corrosion Rate
NOTE:
Air entering the data center must have MERV11
or MERV13 filtration.
Air must be free of conductive dust, zinc whiskers, or other
conductive particles.
Air must be free of corrosive dust.
Residual dust present in the air must have a deliquescent
point less than 60% relative humidity.
<300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985.
<200 Å/month as defined by AHSRAE TC9.9.