B.2 Parameter Table
H2-01
Function
Setting
0
During Run
1
Zero Speed
2
Speed Agree 1
4
Frequency Detection 1
5
Frequency Detection 2
6
Drive Ready
7
DC Bus Undervoltage
8
During Baseblock (N.O.)
B
Torque Detection 1 (N.O.)
E
Fault
F
Not used
10
Minor Fault
17
Torque Detection 1 (N.C.)
1A
Reverse Direction
1E
Restart Enabled
3C
LOCAL/REMOTE Status
3D
Speed Search
100 to
102;
104 to
H2 Parameter Functions
108;
Reversed Output Switching
10B, 10E,
of 0 to 13D
110, 117,
11A, 11E,
13C, 13D
No.
Name
Sets the input level for terminal A1.
Terminal A1
0: 0 to +10 V (lower limit)
H3-01
Signal Level
1: 0 to +10 V (no lower limit)
Selection
2: 4 to 20 mA
3: 0 to 20 mA
H3-03
Terminal A1
Sets the level of the input value when 10 V is input at
<22>
Gain Setting
terminal A1.
H3-04
Terminal A1
Sets the level of the input value when 0 V is input at
<22>
Bias Setting
terminal A1.
208
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
H2 Multi-Function Digital Output Settings
Closed: A Run command is active or voltage is output
Closed: Output frequency is 0
Closed: Output frequency equals the speed reference (plus or
minus 2 Hz)
Closed: Output frequency is less than or equal to the value in
L4-01 plus 2 Hz
Closed: Output frequency is greater than the value in L4-01plus
2 Hz
Closed: Drive Ready. The drive is powered up, not in a fault
state, and in the Drive mode
Closed: DC bus voltage is below the Uv trip level set in L2-05
Closed: There is no output voltage
Closed: Output current/torque exceeds the torque value set in
parameter L6-02 for longer than the time set in parameter L6-03
Closed: Fault occurred (other than CPF00 and CPF01)
Set this value when the terminal is not used, or when using the
terminal in the pass-through mode
Closed: An alarm is triggered
Open: When the output current/torque exceeds the value set in
parameter L6-02 for more time than is set in parameter L6-03
Closed: Drive is running in the reverse direction
Closed: An automatic restart is performed
Closed: LOCAL
Open: REMOTE
Closed: Speed search is being executed
Reverse the output switching of the multi-function output
functions. Set the last two digits of 1oo to reverse the output
signal of that specific function
Examples:
Setting "108" reverses the output of "During baseblock", which
is setting value 08
Setting "13C" reverses the output of "3CLOCAL/REMOTE
Status", which is setting "3C"
Description
H3: Analog Inputs
Use H3 parameters to set the analog input terminals.
Description
Range Def.
0 to 3
0
-999.9 to
100.0
999.9
%
-999.9 to
0.0%
999.9
Mode
V/f
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
Mode Addr.
Pg.
Hex
V/f
O
410
O
411
O
412