No.
Name
Continuous
Determines whether or not to hold the electrothermal
Electrothermal
value when the power supply is interrupted.
L1-13
Operation
0: Disabled
Selection
1: Enabled
Use L2 parameters to configure drive functions for momentary power loss conditions.
Enables and disables the momentary power loss
function.
Momentary
0: Disabled - Drive trips on (Uv1) fault when power
Power Loss
is lost.
L2-01
Operation
1: Power Loss Ride-Thru Time - Drive will restart if
Selection
power returns within the Power Loss Ride-Thru Time.
2: CPU Power Active - Drive will restart if power
returns as long as the CPU is working.
Selects the Stall Prevention method used to prevent
excessive current during acceleration.
Stall
0: Disabled - Motor accelerates at active acceleration
Prevention
rate. The motor may stall if load is too heavy or accel
L3-01
Selection
time is too short.
during
1: General Purpose - When output current exceeds
Acceleration
L3-02 level, acceleration stops. Acceleration will
continue when the output current level falls below the
L3-02 level.
Stall
Used when L3-01 = 1.
Prevention
100% is equal to the drive rated current.
L3-02
Level during
Decrease the set value if stalling or excessive current
Acceleration
occurs with default setting.
When using a braking resistor, use setting "0". Setting
"3" is used in specific applications.
0: Disabled - The drive decelerates at the active
deceleration rate. If the load is too large or the
Stall
deceleration time is too short, an ov fault may occur.
Prevention
1: General Purpose - The drive decelerates at the
L3-04
Selection
active deceleration rate, but if the main circuit DC bus
during
voltage reaches the Stall Prevention level,
Deceleration
deceleration will stop. Deceleration will continue
once the DC bus level drops below the Stall
Prevention level.
4: Overexcitation Deceleration - Decelerates with the
flux level determined by n3-13 (Overexcitation Gain).
Selects the Stall Prevention method to use to prevent
drive faults during run.
0: Disabled - Drive runs a set frequency. A heavy load
may cause the drive to trip on an oC or oL fault.
1: Decel Time 1 - The drive will decelerate at Decel
Stall
Time 1 (C1-02) if the output current exceeds the level
Prevention
set by L3-06. Once the current level drops below the
L3-05
Selection
L3-06 level, the drive will accelerate back to its
during Run
frequency reference at the active acceleration rate.
2: Decel Time 2 - Same as setting 1 except the drive
decelerates at Decel Time 2 (C1-04).
When output frequency is 6 Hz or less, Stall
Prevention during run is disabled regardless of the
setting in L3-05.
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
Description
L2: Momentary Power Loss
L3: Stall Prevention Function
Use L3 parameters to configure the Stall Prevention function.
B.2 Parameter Table
Mode Addr.
Range Def.
V/f
0, 1
1
O
0 to 2
0
O
0, 1
1
O
<63>
0 to 150
<7>
O
0, 1, 4
1
S
0 to 2
1
O
Pg.
Hex
46D
485
48F
490
492
493
B