YASKAWA CIMR-JA Series Installation & Start-Up Manual page 207

Compact v/f control drive
Hide thumbs Also See for CIMR-JA Series:
Table of Contents

Advertisement

H1-oo
Function
Setting
10
Up Command
11
Down Command
14
Fault Reset
15
Fast-Stop (N.O.)
17
Fast-stop (N.C.)
20 to 2F External Fault
Forward Run Command
40
(2-Wire sequence)
Reverse Run Command (2-Wire
41
sequence)
61
External Search Command 1
62
External Search Command 2
67
Communications Test Mode
No.
Name
Use H2 parameters to assign functions to the multi-function digital outputs.
Terminal MA,
MB and MC
Refer to H2 Multi-Function Digital Output Settings
H2-01
Function
on page
Selection
(relay)
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
H1 Multi-Function Digital Input Selections
Open: Maintains the current frequency reference
Closed: Increases or decreases the current frequency reference.
Ensure that the increase and decrease commands are set in
conjunction with one another.
Closed: Resets faults if the cause is cleared and the Run
command is removed.
Closed: Decelerates at the Fast-Stop time C1-09.
To restart the Fast-Stop input must be released and Run must be
cycled.
Open: Decelerates according to C1-09 (Fast-stop Time)
20: N.O., Always Detected, Ramp To Stop
21: N.C., Always Detected, Ramp To Stop
22: N.O., During Run, Ramp To Stop
23: N.C., During Run, Ramp To Stop
24: N.O., Always Detected, Coast To Stop
25: N.C., Always Detected, Coast To Stop
26: N.O., During Run, Coast To Stop
27: N.C., During Run, Coast To Stop
28: N.O., Always Detected, Fast-stop
29: N.C., Always Detected, Fast-stop
2A: N.O., During Run, Fast-stop
2B: N.C., During Run, Fast-stop
2C: N.O., Always Detected, Alarm Only (continue running)
2D: N.C., Always Detected, Alarm Only (continue running)
2E: N.O., During Run, Alarm Only (continue running)
2F: N.C., During Run, Alarm Only (continue running)
Open: Stop
Closed: Forward run
Note: Can not be set together with Settings 42 or 43.
Open: Stop
Closed: Reverse run
Note: Can not be set together with Settings 42 or 43.
Closed: Activates Current Detection Speed Search from the
max. output frequency (E1-04) if b3-01 = 0. Activates Speed
Estimation Type Speed search if b3-01 =1.
Closed: Activates Current Detection Speed Search from the
frequency reference b3-01 = 0. Activates Speed Estimation Type
Speed search if b3-01 =1.
Tests the MEMOBUS/Modbus RS-485/422 interface.
Description
H2: Multi-Function Digital Outputs
208
for a description of setting values.
B.2 Parameter Table
Description
Mode Addr.
Range Def.
0 to 13D
E
Mode
V/f
O
O
O
O
O
O
O
O
O
O
O
Pg.
Hex
V/f
O
40B
103