YASKAWA CIMR-JA Series Installation & Start-Up Manual page 58

Compact v/f control drive
Hide thumbs Also See for CIMR-JA Series:
Table of Contents

Advertisement

3.7 Control Circuit Wiring
NOTICE: Do not tighten screws beyond the specified tightening torque. Failure to comply may damage the
terminal.
NOTICE: Use shielded twisted-pair cables as indicated to prevent operating faults. Improper wiring practices
could result in drive or equipment malfunction due to electrical interference.
Connect control wires as shown in the following figure:
A
S1
S2
S3
S4
S5
A – Control terminal block
B – Avoid fraying wire strands when
stripping insulation from wire. Strip
length 5.5 mm.
C – Single wire or stranded wire
A – Drive side
B – Connect shield to ground terminal of
drive.
C – Insulation
58
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
D
SC
A1
+V
AC AM AC
C
Figure 3.13 Terminal Board Wiring Guide
F
A
B
Figure 3.14 Preparing the Ends of Shielded Cables
Preparing wire
terminal ends
B
D – Loosen screw to insert wire.
E – Blade depth of 0.4 mm or less
Blade width of 2.5 mm or less
C
D
E
D – Control device side
E – Shield sheath (Insulate with tape)
F – Shield
E

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cimr-jt seriesJ1000 series