The parameters are set by setting the bits B0 – B3 in the Permanent
Parameter line. Alternatively, here too, you can save the slave type that has
just been read as permanent parameters by pressing the W
button. The set values are accepted by means of the S
When the parameters of all slaves have been set, save the parameter data in the
master by pressing the S
description of the appropriate slaves for the meaning of the parameters.
In order to assign a new address to the selected slave, enter the number of the
new address in the New Address field and then press the S
of addresses that are already occupied is rejected with an error message.

3.1.6 Observing and setting up AS-Interface process data

The current process data for the selected slave are displayed in the data area.
The input data are shown in the Input line and the output data can be set in
the Output line. In doing so, the values are displayed depending on the
function type. Digital functions are indicated by the states ON / OFF. Analog
functions are displayed in hexadecimal format, as the physical measured
variables relating to the analog inputs and outputs are not known to the master.
The digital output data are set by clicking on the appropriate bits and the
analog output data are are set by entering the hexadecimal value for the
appropriate channel.

3.1.7 AS-Interface diagnostics

The flags in the Properties area for the master are provided for diagnosing the
AS-Interface master.
The status flags are used for information; the operating mode for the AS-
Interface master can be set with the control flags in the right-hand column.
The list of all the slaves with configuration errors (LCS) and the list of all
slaves, which switch the master off line in the case of a fault (LOS), are
provided for diagnosing the AS-Interface slaves.
The LCS list shows all slaves with configuration errors. The entries in the list
contain the slave address, the number of errors that have occurred since the
last read-out, the configuration ID and the slave description. Errors that occur
and their frequency are stored in the master. In this way, even short-term
errors can be detected. After it has been read out, the error memory is reset.
Select those slaves from the LOS list, which are to switch the master into the
offline state in the case of a configuration error, by clicking the check boxes
next to the slave address. You can mark all slaves with the A
reset all marked entries with the N
WAGO-I/O-SYSTEM 750
I/O Modules
Set up and configuration with WAGO-I/O-CHECK 2
Observing and setting up AS-Interface process data
P
TORE
ARAMETER
button.
ONE
A
RITE
P
ET
ERMANENT
button. Please refer to the
button. Entering
ET
button and
LL
• 49