As-Interface Flags; Mailbox - WAGO -I/O-SYSTEM 750 Series Manual

Fieldbus independent i/o modules,
Hide thumbs Also See for WAGO-I/O-SYSTEM 750 Series:
Table of Contents

Advertisement

28 •
750-655 [AS-Interface master module]
Process image
2.1.1.7.3.1

AS-Interface flags

F0
F1
F2
F3
ConfigError:
APF:
PeripheryFault:
ConfigurationActive:
Offline:
LOS master bit:
All bits in the LOS are set with a rising edge of the LOS master bit. All bits in
the LOS are reset with a falling edge of the LOS master bit.
2.1.1.7.4

Mailbox

As well as the 32 bytes of input and output data, an AS-Interface master
manages a large amount of configuration and parameter data. These data are
only required for setting up the AS-Interface circuit and for diagnostics and
therefore only have to be read or written occasionally.
In addition, the master supports slaves according to profile S-7.3 and S-7.4
and other multiplexing slaves, whereby large amounts of data can also occur.
Access is made to these non-time-critical data via the mailbox.
Input data
ConfigError
APF
PeripheryFault
ConfigurationActive
0 Config OK
1 Config error
0 AS-Interface power OK
1 AS-Interface power failed
0 Periphery OK
1 Periphery fault
0 Configuration inactive, master in protected mode
1 Configuration active, master in set-up mode
0 Online
1 Offline
0 Offline with ConfigError deactivated
1 Offline with ConfigError activated
Flags
Output data
Offline
LOS master bit
A rising edge switches the
master to the set-up mode
A rising edge switches the
master to the protected mode
WAGO-I/O-SYSTEM 750