2.1.1.9.2.2

Communications control (Register 57)

Register 57 is used for the control and diagnostics of the parameter channel.
Bit
Request
parameter
Response
parameter
Bit
Request
parameter
Response
parameter
Request
parameter
Response
parameter
Parameter
A0 ... A7
TGL_MS
PRM_RW
MORE_PRM
TGL_SM
TIMEOUT
WAGO-I/O-SYSTEM 750
I/O Modules
Register 57 parameter channel register 1
7
6
5
2
2
2
A7
A6
A5
A7
A6
A5
15
14
13
2
2
2
TGL_
PRM_
MORE_
MS
RW
PRM
TGL_
TIME
BUF_
SM
OUT
OVF
Information is written by the application and read by the module
Information is written by the module and read by the application
Value range
Meaning
0 ... 255
Word address of the parameter to be currently
written/read.
FALSE,
Toggle bit for transmitting new orders from the
TRUE
application to the module. If TGL_SM and TGL_MS
have the same status, a new order has not yet been
initiated. If the flags have different statuses, a new order
has been initiated and is currently being processed.
FALSE
Parameter data are being read from A7 ... A0
TRUE
Parameter data are being written to A7 ... A0
FALSE
Parameter transmission is complete.
TRUE
Further parameter data are to follow
FALSE,
Toggle bit for signaling the acceptance of a transmitted
TRUE
parameter on the part of the module. If the status of
TGL_SM is not the same as that of TGL_MS, then the
respective order is being processed by the module. If both
flags have the same status, then the order for the
previously sent or requested parameter has been
completed.
FALSE
The transmission of the parameters has been completed in
the agreed time (parameter address 0).
TRUE
The maximum transmission time for the parameters
previously negotiated between the module and the
application has been exceeded.
750-655 [AS-Interface master module]
Data channel for parameter exchange
4
3
2
2
2
2
A4
A3
A2
A4
A3
A2
12
11
10
2
2
2
RES
RES
RES
PRM_
RES
RES
ERR