Set actual configuration data (STORE_CDI, 0x07)
STORE_CDI: Store_Actual_Configuration
The "ACTUAL" configuration data (I/O configuration, ID code, extended ID1
code and extended ID2 code) of all AS-Interface slaves detected on the AS-
Interface are stored in the non-volatile memory as (REQUIRED) configuration
data with this call. The list of activated slaves (LAS) is similarly incorporated
into the list of set-up AS-Interface slaves (LPS).
When this command is executed, the AS-Interface switches the master into the
offline phase and then returns to normal mode (restart AS-Interface master).
This command is only executed in set-up mode.
Byte
Byte
WAGO-I/O-SYSTEM 750
I/O Modules
Request
7
6
5
2
2
2
1
2
T
-
Response
7
6
5
2
2
2
1
2
T
Mailbox command - Reference
4
3
2
1
2
2
2
2
0x07
-
4
3
2
1
2
2
2
2
0x07
Result
Appendix
0
2
0
2
• 81