144 Electrical installation – IEC

Additional information on I/O connections

PNP configuration for digital inputs

Internal and external +24 V power supply connections for PNP configuration are shown
in the figure below.
Internal +24 V power supply
PNP connection (source)
X2 & X3
10
11
12
13
14
15
16
17
18
WARNING!
Do not connect the +24 V AC cable to the control unit ground when the control
unit is powered from an external 24 V AC supply.

NPN configuration for digital inputs

Internal and external +24 V power supply connections for NPN configuration are shown
in the figure below.
Internal +24 V power supply
NPN connection (source)
Note: DI6 is not supported in the NPN configuration.
WARNING!
Do not connect the +24 V AC cable to the control unit ground when the control
unit is powered from an external 24 V AC supply.
+24V
DGND
DCOM
DI1
DI2
DI3
DI4
DI5
DI6
X2 & X3
10 +24V
11 DGND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
External +24 V power supply
PNP connection (source)
X2 & X3
10
0 V DC
11
+24 V DC
12
13
14
15
16
17
18
External +24 V power supply
NPN connection (source)
X2 & X3
10 +24V
11 DGND
+24 V DC
12 DCOM
0 V DC
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
+24V
DGND
DCOM
DI1
DI2
DI3
DI4
DI5
DI6