112 Technical data
Input
current
ACS180-04...
-17A5-2
21.2
-25A0-2
27.2
-033A-2
-048A-2
48
-055A-2
60
3-phase U n = 380 ... 415 V
-01A8-4
2.8
-02A6-4
3.6
-03A3-4
4.6
-04A0-4
6.3
-05A6-4
-07A2-4
-09A4-4
-12A6-4
17.4
-17A0-4
25.2
-25A0-4
31.8
-033A-4
40.9
-038A-4
49
-045A-4
55.7
-050A-4
55.7
1) Minimum permitted short-circuit current of the electrical power network

UL (NEC) fuses

The UL listed fuses in the table are the required branch circuit protection. Fuses
must be provided as part of the installation.
current
ACS180-04...
1-phase U n = 208 ... 240 V
-02A4-1
Min. short-
circuit cur-
1)
rent
A
A
656
400
35
504
800
800
47
60
87
116
9
174
12
230
13
258
440
560
400
504
640
800
800
Input
Min. short-cir-
cuit current
A
A
4.8
62
Nominal
I 2 t
current
A 2 s
A
50
2200
80
5448
100
6650
160
11700
160
11700
20
170
20
170
20
170
25
333
25
333
32
679
32
679
50
2200
50
2200
80
3600
100
6650
125
7300
160
11700
160
11700
Nominal
Voltage
current
rating
A
V
6
300
Voltage
rating
Bussmann type
V
690
FWP-50G14F
690
FWP-80G22F
690
FWP-100G22F
700
FWP-150A
700
FWP-150A
690
FWP-20G14F
690
FWP-20G14F
690
FWP-20G14F
690
FWP-25G14F
690
FWP-25G14F
690
FWP-32G14F
690
FWP-32G14F
690
FWP-50G14F
690
FWP-50G14F
690
FWP-80G22F
690
FWP-100G22F
700
FWP-125A
700
FWP-150A
700
FWP-150A
Buss-
mann
Type
type
JJN-6
UL class T