2.1.3.4 Setting the Intelligent Detection Card

Prerequisites
An intelligent detection card is installed.
Procedure
Step 1 On the LCD, choose System Info > Settings > System Settings and set
Intelligent detection module to Enable.
----End

2.1.3.5 Setting Parameters for the Bottom Cabling Cabinet

Prerequisites
A bottom cabling cabinet is installed.
Procedure
Step 1 On the LCD, choose System Info > Settings > System Settings and set Bottom
cable entry cabinet to Enable.
----End

2.1.4 Setting Working Modes

2.1.4.1 Setting the ECO Mode

Prerequisites
The UPS is working in inverter mode.
Context
Issue 01 (2023-03-20)
NO TE
If MUE06A connection is set to Enable and the backfeed protection card fails to
communicate with the UPS, the system reports a Dry contact board fault alarm.
The UPS is set to non-ECO mode by default. Set the UPS to ECO mode when
it is required.
In ECO mode, the bypass takes priority over the inverter in supplying power. If
the bypass fails, the UPS transfers to inverter mode.