Figure 27: Examples of ringlug
Table 9:
Connector type
Screw compression type
Terminal blocks suitable for ring lug terminals
6.1.5

Connecting the binary input and output signals

Auxiliary power and signals are connected using voltage connectors. Signal wires are connected to
a female connector (see Figure 29) which is then plugged into the corresponding male connector
(see Figure 30) located at the rear of the IED. For location of BIM, BOM, SOM and IOM refer to
section
"Rear side
Figure 17, Figure 21, Figure
670 series
Installation manual
terminals
CT and VT circuit connectors
connectors". Connection diagrams for BIM, BOM, SOM and IOM are shown in
22
and Figure 23.
Do not insert anything else to the female connector but the corresponding male
connector. Inserting anything else (such as a measurement probe) may violate the
female connector and prevent a proper electrical contact between the printed
circuit board and the external wiring connected to the screw terminal block.
IEC06000506 V1 EN-US
Figure 28: Examples of standard
compression connection
terminals
Rated voltage and current
250 V AC, 20 A
250 V AC, 20 A
Section 6
Connecting
SEMOD53376-2 v6
Maximum conductor area
2
4 mm
(AWG12)
2
2 x 2.5 mm
(2 x AWG14)
2
4 mm
(AWG12)
M11992-9 v8