Motion Detect Setting Method - Unipulse F350 Operation Manual

Digital indicator
Table of Contents

Advertisement

5 EXPLANATION OF INDICATED- VALUE-RELATED FUNCTIONS
Setting example
Chapter
5

■Motion Detect setting method

42
42
Motion Detect (time)
Motion Detect (range)
Indicated value
d
50msec.
When the condition of dn ≦ set count (10) continues for the set time (0.4 sec.) or more
(d1 ≦ 10, and d2 ≦ 10, and ..., and d8 ≦ 10), the indicated value is regarded as stable.
1.
Select setting mode2.
Press
FNC
2.
Set "Motion Detect."
Press
once. ⇒ "Motion Detect" is displayed.
Press
, and the highest digit blinks.
① Set " Motion Detect time."
Input the setting value with
Move to the lower digits with
(Initial value: 0.0)
② Set " Motion Detect range."
Input the setting value with
Move to the lower digits with
(Initial value: 00)
Press
to validate it.
3.
Press
twice to go back to the indicated value display.
ESC
0.4 sec.
10
Motion Detect time ( 0.4sec.)
d
d
4
d
3
d
2
1
dn = 50msec. difference of the previous
instruction value
once.
.
.
.
.
d
8
d
7
5
d
6
Ch1 Ch 2
H I
LO
H I
OK
LO
Ch1 Ch 2
H I
LO
setting value
.
-
0
0
0
Time
0.0 ~ 9.9
【second】
Time
H I
LO
PEAK
HOLD
H I
LO
0
Range
00 ~ 99
【count】

Advertisement