Installation manual
DAN-20057315
10. Select the settings below to configure a serial port as a Modbus Master to poll a gas
11. Configure the Component indexes and the C6+ split. This page is available for
12. Configure the properties necessary for the AGA8 calculations.
Model 3418 GUSM
chromatograph. See
Serial Connections
Serial Port: select which serial port will be connected to the GC. While the port is
configured for communications to a GC, it will not act as a Modbus slave device
for communications from Daniel MeterLink
GC protocol: select the protocol for which the GC is configured. The Daniel Gas
Ultrasonic meter uses 7 data bits, Even parity, and 1 stop bit for ASCII Modbus
and 8 data bits, No parity, and 1 stop bit for RTU Modbus.
GC baud rate: select the baud rate for which the GC is configured.
GC comms address: enter the Modbus ID of the GC.
GC stream number: enter the stream number for the gas composition the Daniel
Gas Ultrasonic meter will read.
GC heating value units: elect the units for which the heating value is configured
in the GC.
Use which gas composition on GC alarm: select which gas composition the
Daniel Gas Ultrasonic meter will use if the GC goes into alarm. If Fixed value is
selected, the meter will start using the fixed gas composition stored in the
meter. If Last good value is selected, the meter will use the last gas composition
collected from the GC before the GC started to report alarms.
a) Click Next to continue to the Gas Chromatograph Data.
Daniel Gas Ultrasonic meters and displayed only if View Gas Chromatograph
checkbox was selected on the Startup page and if the Gas Chromatograph Setup
page was previously displayed.
a) Click Next to continue to the AGA8 page.
This page is only displayed for Daniel Gas Ultrasonic meters if both temperature and
pressure are set to Live Analog, Fixed and Base condition correction is selected on
the Startup Page. Configuration parameters include:
Calculations performed internally (by the meter) or Externally
AGA8 method - Gross Method 1, Gross method 2, Detail or GERG-2008
GC composition source - Fixed, Live GC
Base temperature and pressure
Specific gravity - reference temperature and pressure
Volumetric gross heating value and reference temperature
Molar density reference temperature and pressure
Flow Mass density, flow compressibility and Base compressibility
Gas composition inputs - components and mole percent
to configure port as Read-only.
or a SCADA system.
Configuration
June 2019
85