Operating Behavior in Conjunction with PROFINET
I
6
MOVITRAC® B (gateway) – control
0 0
6.5
MOVITRAC
58
®
B (gateway) – control
The inverter is controlled via the process data channel, which is up to 3 I/O words in
length. These process data words may be mapped in the I/O or peripheral area of the
controller if a programmable controller is used as IO controller and can be addressed as
usual.
PO 3
POW318
[1]
PO 2
POW316
PO 1
POW314
PO 3
POW312
[2]
PO 2
POW310
PO 1
POW308
PI 3
PIW318
PI 2
PIW316
PI 1
PIW314
PI 3
PIW312
PI 2
PIW310
PIW308
PI 1
Figure 3: Mapping PROFINET data in the PLC address range
[1]
Address range MOVITRAC
[2]
Address range MOVITRAC
PO = process output data / PI = process input data
PO 1
PO 2
PO 1
PO 3
®
MOVITRAC
B 1
MOVITRAC
PI 2
PI 3
PI 1
PI 1
®
B, unit 2
®
B, unit 1
Manual – DFE32B Fieldbus Interface PROFINET IO
PO 2
PO 3
®
B 2
PI 2
PI 3
58612AXX