KEB Combivert F5 Instruction Manual page 50

Lift
Hide thumbs Also See for Combivert F5:
Table of Contents

Advertisement

Parameter description
LI.12
Actual load
Display
0...200 %
LI.13
Peak load
Display
0...200 %
LI.14
Actual DC link voltage
Display
0...1000 V
LI.15
Peak value DC link voltage
Display
0...1000 V
LI.16
Active parameter set
Display
0...7
LI.17
Terminal input status
Decimal
value
1
2
4
8
16
32
64
128
256
512
1024
2048
GB -50
Description
Description
Description
Display of the current DC link voltage in volt. Typical values are:
V-class
Normal operation
230 V
300...330 V DC
400 V
530...620 V DC
Description
This parameters makes it possible to determine short-term voltage rises within an
operating cycle. For that purpose the highest value that occurred is stored. The peak
value memory can be cleared by pressing the key UP, DOWN or ENTER and over Bus by
writing any value onto this parameter. Switching off the inverter also results in the deletion
of the memory.
Description
Display of the parameter set, in which the frequency inverter currently works.
Input
Function
X2A.16
X2A.17
X2A.14
X2A.15
X2A.10
Display of the currently activated digital inputs. The logical levels at the digital inputs
X2A.11
and at the internal inputs are indicated, independent of the following linkage. A certain
decimal value is given out for each digital input. If several inputs are activated, the
X2A.12
sum of the decimal value is displayed.
X2A.13
internal A
internal B
internal C
internal D
Overvoltage (E.OP)
ca. 400 V DC
ca. 800 V DC
Undervoltage (E.UP)
ca. 216 V DC
ca. 240 V DC