Parameter Description
Ld.05
Cos phi
Value range
0,5...1,0
Ld.06
Rated voltage
Value range
120...830 V
Ld.07
Calibration of winding resistance (only at Lb.03 = A G or A GL)
Value range
0
1
Ld.08
Winding resistance
Value range
0,00...250,00 Ω
Ld.09
Winding inductance (only at LB.03 = S G or S GL)
Value range
0,00...500,00 mH
Ld.10
Rated torque
Value range
0,0...xxx,0 Nm
GB - 28
Setting
Description
-
Input of the cos phi of the motor according to motor name plate.
Setting
Description
400 V
Input of the motor rated voltage according to motor name plate.
Setting
Description
x
Basic position before and after the automatic calibration.
Bring motor to working temperature
Activate calibration mode by setting „1"
Set drive command (e.g. return)
Set control release
Press UP (▲) -key in Ld.08 once shortly
The calibration starts and is completed after approx. 10 s
Ld.08 displays now the measured value
Cancel the drive command
Open control release, thereby the measure procedure is finished
Setting
Description
249,99 Ω With this parameter the direct input of the motor winding resistance can be
made.
Measure with a multimeter:
The motor resistance is measured, independent of the motor connection (∆/Y),
between two phases of the motor feed line. That way the ohmic line resistance
is recorded at the same time (important in case of long feed lines). At that the
motor should be at working temperature.
Input of the motor winding resistance according to data sheet:
When taking the motor resistance from a data sheet, the R120 - equivalent
resistance (phase value) is mostly specified there. Then the following values,
depending on the used connection, must be adjusted in Ld.08 :
Star connection: Ld.08 = 2 • R1
Delta connection: Ld.08 = 0,666 • R1
If only the warm resistance R1W is specified:
Star connection: Ld.08 = 1,4 • R1
Delta connection: Ld.08 = 0,46 • R1
Setting
Description
x,x mH
Input of the leakage inductivity of the motor winding.
When taking the leakage inductivity from a data sheet, the phase value for
σLS is mostly specified there. Then the following value, depending on the
used connection, must be entere in Ld.09:
Star connection: Ld.09 = 2 x σLS
Delta connection: Ld.09 = 2/3 x σLS
Setting
Description
xx Nm
Input of the motor rated torque of the synchronous machine according to the
data sheet. The value is automatically calculated at asynchronous machines
to 2,24 • R1
20
20
to 0,75 • R1
20
20
to 1,6 • R1
W
W
to 0,53 • R1
W
W