Parameter Description
LF.60
Indication levelling path
Value range
0,0...264,0 cm
V
V
N
V
E
Deceleration point
Levelling path optimization V
With the levelling distance optimization the levelling path become shorter by the entered value. 3...5 cm levelling
path are sufficient. Measuring the levelling distance with LF.60.
LF.61
Levelling path optimization VN
Value range
0,0...200,0 cm
LF.62
Levelling path optimization V1
Value range
0,0...200,0 cm
LF.63
Levelling path optimization V2
Value range
0,0...200,0 cm
LF.64
Levelling path optimization V3
Value range
0,0...200,0 cm
LF.65
Levelling path optimization VL
Value range
0...300 mm
Setting
Description
-
The time of constant drive in crawl speed (VL) is measured and displayed
after each run in standardized cm. .
without optimization
N
Setting
Description
0,0 cm
Out of operation at ogive function.
Setting
Description
0,0 cm
Setting
Description
0,0 cm
Setting
Description
0,0 cm
Setting
Description
0 mm
V
V
N
V
E
t
Deceleration point
LF.61
with optimization
t
GB - 43