Configuration Example - Samson TROVIS 6495 Series Mounting And Operating Instructions

Industrial controller
Table of Contents

Advertisement

1x Enter menu.
The first submenu is highlighted.
... If the configuration item that you
want to set is not in the highlighted
submenu, select the required
submenu.
1x Enter submenu.
The first configuration item of the
submenu is displayed together with
its current setting.
Note: The menu C Controller partly con-
sists of two submenu levels. To view the indi-
vidual configuration items, the submenus
must be entered one after the other.
... If you want to set another configura-
tion item or parameter other than the
one displayed, select the required
configuration item/parameter.
1x Activate configuration item/parame-
ter.
Change configuration item/parame-
ter.
1x Confirm setting.
Return to the operating level
... Return to the operating level
stepwise.

9.2.2 Configuration example

Based on a default setting (1x Fixed set
point/follow-up control M.1-1), the analog
input AI1 is to be set to Pt 1000. The mea-
suring range is to be 0 to 200 °C.
ü
The code of the configuration item to
determine the input signal is I.1.1,
see configuration list (section 15.2).
Lower and upper range values are
set in the AI1.MIN and AI1.MAX
parameters. Both parameters are as-
signed to the configuration item
I.1.1.
ü
The following position in the configu-
ration level can be found using the
code of the configuration item:
4
→ Menu I Input
I
4
→ Submenu 1
I.1
Analog input AI1
4
I.1.1 → Configuration item 1
Input signal
Note: The analog input AI1 can only be
configured as a Pt 1000 input when the DIP
switches are positioned for "Pt 100/
Pt 1000".
Both DIP switches AI1 (at the side of the con-
troller case) must set to the position "Pt 100/
Pt 1000" (see Fig. 3 on page 12).
Configuration menu
31
EB 6495-2 EN