Samson TROVIS 6495 Series Mounting And Operating Instructions page 70

Industrial controller
Table of Contents

Advertisement

Appendix
4 digital inputs
Control
Outputs
3 analog outputs
Nominal signal range
Max. permissible signal
range
Load
Error of outputs
Ambient temperature
influence
Resolution
Static destruction limit
7 digital outputs
Relay
4 relays with floating NO contact, can be inverted
outputs
Permissible contact load
Spark suppression
Transistor
3 electrically isolated transistor outputs
outputs
External supply
Interfaces
Infrared
Transmission protocol
interface
Data that can be
transmitted
Transmission rate
Angle of deflection
Distance IR adapter –
controller
70
EB 6495-2 EN
Floating switching contact or external switching voltage
24 V DC, 3 mA; two digital inputs both are galvanically
connected on one side;
Signal state "OFF": 0 to 10 V; signal state "ON": 17 to
31 V; adjustable signal inversion
0 to 20 mA, 4 to 20 mA, 0 to 10 V, 2 to 10 V
0 (2.4) to 22 mA or 0 (1.2) to 11 V
< 750 Ω for current; > 3 kΩ for voltage
< ± 0.2 % of the nominal signal range for zero, span,
linearity
< ± 0.1 %/10 K for zero and span, based on 20 °C
< 0.03 %, based on nominal signal range
±30 V
264 V AC, 1 A AC, cos φ = 1 or 250 V DC, 0.1 A DC
Connected in series C = 2.2 nF and varistor 300 V AC,
in parallel to each relay contact
3 to 42 V DC, max. 30 mA
SAMSON-specific protocol (SSP)
Controller settings, processs variables, operating status
9600 bit/s
50°
≤ 70 cm

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Trovis 6495-2

Table of Contents