Configuration menu
1x Enter menu 1C Controller [1].
The submenu 1C.1 Input
variables is highlighted.
4x Select submenu 1C.5 Controller
display.
1x Enter submenu 1C.5 Controller
display.
The configuration item 1C.5.1 Row
1 is displayed together with the cur-
rent setting: 1C.5.1-1 = Actual
value PV0 at comparator
5x Select configuration item 1C.5.6
Row 5.
The currently active setting is dis-
played: 1C.5.6-0 = Off
1x Activate configuration item 1C.5.6.
The currently active setting is
highlighted: Off
34
EB 6495-2 EN
2x Change setting to 1C.5.6-2
(Output AO1).
1x Confirm setting.
Configure row representation
1x Select configuration item 1C.5.7
Row 5 representation.
The currently active setting is dis-
played: 1C.5.7-1 = Numerical
1x Activate configuration item 1C.5.7.
The currently active setting is high-
lighted: Numerical
2x Change setting to 1C.5.7-3 (Bar
graph).
1x Confirm setting.