Samson TROVIS 6495 Series Mounting And Operating Instructions page 117

Industrial controller
Table of Contents

Advertisement

O.1.1
Assign source
[2] Error signal +/–e <M.1-3/-4/-5/-6>
-35
[2] Error signal e <M.1-3/-4/-5/-6>
-36
Output master controller YM <M.1-3>
-37
Y1 ∗ Y2 ∗ AO1.KM/100 <M.1-5/-6>
-38
(100 – Y1) ∗ Y2 ∗ AO1.KM/100 <M.1-5/-6>
-39
AO1.FX
Constant output value <O.1.1-4>
Constant, mixing operation <O.1.1-38/-39> [0.0 ... 100.0]
AO1.KM
O.1.2
Output signal <O.1.1≠0>
4–20 mA
-1
0–20 mA
-2
0–10 V
-3
2–10 V
-4
AO1.MIN
Minimum output value
AO1.MAX
Maximum output value
O.1.3
Operating direction <O.1.1≠0>
Increasing
-1
Decreasing
-2
AO1.P1
Y value for AO1=AO1.MIN <O.1.3-1>
Y value for AO1=AO1.MAX <O.1.3-2>
The default value of AO1.P1 is the same as AO1.MIN.
If AO1.MIN is changed, AO1.P1 is set to AO1.MIN.
AO1.P2
Y value for AO1 = AO1.MAX <O.1.3-1>
Y value for AO1 = AO1.MIN <O.1.3-2>
The default value of AO1.P2 is the same as AO1.MAX.
If AO1.MAX is changed, AO1.P2 is set to AO1.MAX.
O.1.4
Output ramp <O.1.1≠0, O.1.5-0>
Off
-0
Start with DI1
-1
Start with DI2
-2
Start with DI3
-3
Start with DI4
-4
AO1.GD
Gradient <O.1.4≠0>
AO1.TB
Time base <O.1.4≠0>
AO1.ST
Initial value<O.1.4≠0>
O.1.5
Limit output rate <O.1.1≠0, O.1.4-0>
Off
-0
Increasing, continuously active
-1
Default
setting
[–10.0 ... 110.0 %]
0.0 %
O.1.2-1
[–10.0 ... 110.0 %]
[–10.0 ... 110.0 %]
100.0 %
O.1.3-1
[–10.0 ... 110.0 %]
0.0 %
[–10.0 ... 110.0 %]
100.0 %
C.1.4-0
[0.1 ... 100.0 %]
1.0 %
[s, min, h]
[–10.0 ... 110.0 %]
0.0 %
O.1.5-0
Appendix
Setting
1.0
0.0 %
s
117
EB 6495-2 EN