Appendix
AO3.FX
Constant output value <O.3.1-4>
Constant, mixing operation <O.3.1-38/-39> [0.0 ... 100.0]
AO3.KM
O.3.2
Output signal <O.3.1≠0>
4–20 mA
-1
0–20 mA
-2
0–10 V
-3
2–10 V
-4
AO3.MIN
Minimum output value
AO3.MAX
Maximum output value
O.3.3
Operating direction <O.3.1≠0>
Increasing
-1
Decreasing
-2
AO3.P1
Y value for AO3=AO3.MIN <O.3.3-1>
Y value for AO3=AO3.MAX <O.3.3-2>
The default value of AO3.P1 is the same as AO3.MIN.
If AO3.MIN is changed, AO3.P1 is set to AO3.MIN.
AO3.P2
Y value for AO3 = AO3.MAX <O.3.3-1>
Y value for AO3 = AO3.MIN <O.3.3-2>
The default value of AO3.P2 is the same as AO3.MAX.
If AO3.MAX is changed, AO3.P2 is set to AO3.MAX.
O.3.4
Output ramp <O.3.3-1, O.3.5-0>
Off
-0
Increasing, start with DI1
-1
Increasing, start with DI2
-2
Increasing, start with DI3
-3
Increasing, start with DI4
-4
AO3.GD
Gradient <O.3.4≠0>
AO3.TB
Time base <O.3.4≠0>
AO3.ST
Initial value<O.3.4≠0>
124
EB 6495-2 EN
Default
[–10.0 ...110.0 %]
O.3.2-1
[–10.0 ... 110.0 %]
[–10.0 ... 110.0 %]
100.0 %
O.3.3-1
[–10.0 ... 110.0 %]
[–10.0 ... 110.0 %]
100.0 %
O.3.4-0
[0.1 ... 100.0 %]
[s, min, h]
[–10.0 ... 110.0 %]
Setting
setting
0.0 %
1.0
0.0 %
0.0 %
1.0 %
s
0.0 %