6. Configuration and parameterization

The controller configuration und parameterization are entered on the installation level.
After accessing the installation level, the function blocks F1 to F6 appear first of all, followed
by the parameters P1 to P15 and finally the measured temperatures t1 to t4.
You can select function blocks, parameters and measured temperatures you require by turn-
ing the control knob.
Set the function blocks to 1 = ON or 0 = OFF depending on the function required. Set the
parameters to any value within a predetermined value range.
The function blocks and parameters are listed together with their meaning and default setting
in the table on page 20 and 21.

6.1 Accessing the installation level

Press the control knob for three seconds to change over
from the display level to the user level.
At first, the time appears in the display.
Turn the control knob clockwise or counterclockwise until
End appears in the display.
Press the knob again for 3 seconds,
the installation level is opened when the first function block
F1 appears in the display.
Now you can continue to all other function blocks, to the
parameters and the temperatures by turning the control
knob.
To make any changes, press the control knob when you
reach the function block or parameter you want to change.
Turn the knob to set and press it to acknowledge the new
setting.
Configuration and parameterization
EB 5432-1 EN
19