Configuration menu
The controller is currently in the operating
level:
4
Enter the configuration level, see sec-
tion 9.1.
Configure the input signal
1x Select menu I Input.
1x Enter menu I Input.
The submenu I.1 Analog input
AI1 is highlighted.
1x Enter submenu I.1 Analog in-
put AI1.
The configuration item I.1.1 Input
signal is displayed together with the
current setting: I.1.1-6 = Pt 100
1x Activate the configuration item I.1.1
Input signal.
32
EB 6495-2 EN
The input signal setting is high-
lighted: Pt 100
1x Change setting to I.1.1-7
(Pt 1000).
1x Confirm new setting.
Set the measuring range
1x Select AI1.MIN Lower range
value parameter.
The lower range value is already set
to 0 °C and does not need to be
changed.
1x Select AI1.MAX Upper range
value parameter.
1x Activate AI1.MAX Upper range
value parameter.
The upper range value setting is
highlighted: 100.0 °C
... Keep pressed and change the upper
range value to 200 °C.
1x Confirm new setting.