Samson TROVIS 6495 Series Mounting And Operating Instructions page 26

Industrial controller
Table of Contents

Advertisement

Operating menu
Required configuration for determining the set
point
SP1
SP2
SP3
SP4
Example: The controller [1] has two internal
set points SP1 and SP2 (configured with
1C.2.1.1-2).
• The set point SP1 is to be switched over to
set point SP2.
• The set point SP1 is to be kept at 70 while
the set point SP2 is to be changed to 100.
The controller is currently in the operating
level:
4
Enter the operating menu (see section
8.1).
Switchover between internal set points
1x Select the menu item Set point.
26
EB 6495-2 EN
C.2.1.1-1/-2/-3/-4
C.2.1.1-2/-3/-4
C.2.1.1-3/-4
C.2.1.1-4
1x Activate the menu item Set point
The actual value at the comparator
PV0 (
), the set point at the com-
parator SP0 (
lated variable Y (
on the left. For ratio control: Actual
ratio PVR, ratio set point SPR and
manipulated variable Y). Their
course within the last minute in the 0
to 100 % range of the measuring
range is plotted on the right.
The assignment of the internal set
point (in this case: SPI = SP1) is indi-
cated below.
1x Activate the internal set point.
The current internal set point is high-
lighted: SP1
1x Set the internal set point SPI = SP2.
1x Confirm the setting
SP2 is now the active set point.
Change set points SP1 and SP2
1x Select the set point SP1.
) and the manipu-
) are indicated