CONFIGURATION level

6.4.2. Example how to modify a configuration block

This section describes how to modify a configuration block, using C5 (configuration of controller
outputs) as an example. All other configuration blocks have to be modified accordingly.
Fig. 25
Fig. 27
Fig. 29
38
Fig. 26
Fig. 28
Fig. 30
Fig. 25
The process control station is in the standard
operating mode and the display is, for exam-
ple as shown in Fig. 25 .
Fig. 26
Press A key. I-O comes up on the display.
Fig. 27
Press C key twice. CO appears on the display.
Fig. 28
Press A key. The configuration block modified
last and its setting are displayed (here C 8
and -1).
Fig. 29
Press C or D several times until C 5 is display-
ed. The valid setting for C 5 (here - 2) is
shown in the upper line of the display.
Fig. 30
Press A key.
If no code number was entered (factory de-
fault) CO flashes on the display. Hold down
the A key for approximately 3 s.
If a code number was entered (not shown in
this figure), CO and
keys to set the code number in the upper line
of the display (3). Then, press A key.
Operation