7 Start-up and configuration

7.1 Initializing the actuator

The initialization process starts automatically
after the actuator has been connected to the
supply voltage. The actuator stem extends
(when the direction of action increasing/in-
creasing has been set) and the red and yel-
low LEDs underneath the cover on top of the
actuator are illuminated. As soon as the ac-
tuator stem has reached the final position,
the red LED is turned off. The yellow LED re-
mains illuminated and indicates that the ac-
tuator is ready for use.
Blinking pattern of the red LED:
Zero calibration in progress
On
Off
Blinking pattern of the yellow LED (after
initialization):
Device ON
On
Off
EB 5757 EN

7.2 Configuring the actuator

The actuator is configured with the TROVIS-
VIEW software. In this case, the serial
interface on the actuator is used to connect
the actuator to the computer (see the 'Design
and principle of operation' section).
Î Refer to u EB 6661 and u KH 5757 for
more details on configuration and opera-
tion using TROVIS-VIEW.
Note
The Configuration Manual u KH 5757 can
be found in the Help menu of the TROVIS-
VIEW software. The manual contains a
detailed description of each function and
parameter.