Samson TROVIS 6495 Series Mounting And Operating Instructions page 127

Industrial controller
Table of Contents

Advertisement

SO1.TY
Transit time <O.4.2-1/-5>
SO1.TZ
Dead zone <O.4.2≠0>
SO1.SW
Increment <O.4.2-1/-2>
SO1.P+
Duty cycle (+) signal <O.4.2-3/-4/-5/-6>
SO1.P–
Duty cycle (–) signal <O.4.2-5/-6>
SO1.TMIN+
Minimum on-time (+) signal
<O.4.2-3/-4/-5/-6>
SO1.TMIN–
Minimum on-time (–) signal <O.4.2-5/-6>
SO1.TMAX+
Maximum on-time (+) signal
<O.4.2-3/-4/-5/-6>
SO1.TMAX–
Maximum on-time (–) signal
<O.4.2-5/-6>
SO1.MIN
Minimum output value <O.4.2≠0>
SO1.MAX
Maximum output value <O.4.2≠0>
O.4.3
Operating direction <O.4.1≠0>
Increasing
-1
Decreasing
-2
SO1.P1
Y value for SO1=SO1.MIN <O.4.3-1>
Y value for SO1=SO1.MAX <O.4.3-2>
The default value of SO1.P1 is the same as SO1.MIN.
If SO1.MIN is changed, SO1.P1 is set to SO1.MIN.
SO1.P2
Y value for SO1 = SO1.MAX <O.4.3-1>
Y value for SO1 = SO1.MIN <O.4.3-2>
The default value of SO1.P2 is the same as SO1.MAX.
If SO1.MAX is changed, SO1.P2 is set to SO1.MAX.
O.4.4
Output ramp <O.4.1≠0>
Off
-0
Start with DI1
-1
Start with DI2
-2
Start with DI3
-3
Start with DI4
-4
SO1.GD
Gradient <O.4.4≠0>
SO1.TB
Time base <O.4.4≠0>
SO1.ST
Initial value<O.4.4≠0>
Default
setting
[10 ... 1000 s]
[0.1 ... 100.0 %]
2.0 %
[1 ... 4]
[1.0 ... 1000.0 s]
10.0 s
[1.0 ... 1000.0 s]
10.0 s
[0.1 ... 100.0 %]
1.0 %
[0.1 ... 100.0 %]
1.0 %
[0.1 ... 100.0 %]
100.0 %
[0.1 ... 100.0 %]
100.0 %
[0.0 ... 100.0 %]
0.0 %
[0.0 ... 100.0 %]
100.0 %
O.4.3-1
[0.0 ... 100.0 %]
0.0 %
[0.0 ... 100.0 %]
100.0 %
O.4.4-0
[0.1 ... 100.0 %]
1.0 %
[s, min, h]
[–10.0 ... 110.0 %]
0.0 %
Appendix
Setting
60 s
1
s
127
EB 6495-2 EN