Configuration List - Samson TROVIS 6495 Series Mounting And Operating Instructions

Industrial controller
Table of Contents

Advertisement

15.2

Configuration list

Note: Some functions and parameters can only be selected after certain initial settings have
been made beforehand. The inital setting required is specified in angle brackets in the fol-
lowing list. A comma represents "and" and a slash represents "or" in the following list.
Example <M.1-5/-6, I.3.5≠0> : Either the configuration M.1-5 and I.3.5≠0 or the
configuration M.1-6 and I.3.5≠0 must initially be set.
M Control mode
NOTICE
Changing the control mode causes the controller to be reset to its default settings.
M.1
Control mode
1x fixed set point/follow-up control
-1
Ratio control
-2
Cascade control
-3
Override control
-4
2x fixed set point/follow-up control
-5
Ratio control + Controller
-6
I Input
I.1
Analog input AI1
I.1.1
Input signal
4–20 mA <both DIP switches on right: mA/V>
-1
0–20 mA <both DIP switches on right: mA/V>
-2
0–10 V
-3
2–10 V
-4
Via interface
-5
Pt 100
-6
Pt 1000
-7
AI1.MIN
Lower range value
AI1.MAX
Upper range value
<both DIP switches on right: mA/V>
<both DIP switches on right: mA/V>
<both DIP switches on left: Pt 100/Pt 1000>
<both DIP switches on left: Pt 100/Pt 1000>
<I.1.1-6/-7, I.1.3-1>:
<I.1.1-6/-7, I.1.3-2>:
<I.1.1-6/-7, I.1.3-1>:
<I.1.1-6/-7, I.1.3-2>:
[–999.0 ... 9999.0]
[–50.0 ... 300.0 °C]
[–58.0 ... 572.0 °F]
[–999.0 ... 9999.0]
[–50.0 ... 300.0 °C]
[–58.0 ... 572.0 °F]
Appendix
Default
Setting
setting
M.1.1-1
Default
Setting
setting
I.1.1-6
0.0
100.0
73
EB 6495-2 EN