Section 7
IEC 61850 communication engineering
7.3.3
7.3.3.1
108
4.1. Configure GOOSE control blocks for each data set configured for GOOSE
messages.
4.2. Define the client IEDs for each GOOSE control block.
4.3. Link the IEDs to the GOOSE control block that is to receive the GOOSE
control block.
5.
Update the data flow.
6.
Export the updated SCD file.
All data sets, Report Control Blocks and GOOSE control blocks
must be located in LLN0.

Importing SCL files to PCM600

The IED engineering tool must be able to receive a SCD file or an ICD file as an
import to receive the engineered communication extensions, for example, for the
different IEDs.

Importing SCD files

1.
Select the station in the Plant Structure view.
2.
Right-click the station and select Import.
3.
From the open standard Windows menu, select the file to be imported and start
the reading.
The SCL Import Options dialog box opens, quering how the file should be
handled during the import.
One data must be included only once in the GOOSE data set.