Section 4
Setting up a project
4.10
60
GUID-6F47B4AD-B956-4F77-A6A2-DE6F4A71D607 V1 EN
Figure 40:
Creating a new 615 series device into SAB600 project
5.
Check the default settings in the SCL Import view and change the settings if
they are not suitable.
The default settings in the SCL Import dialog should be OK in most cases.
6.
Click Import to import the SCD file.
7.
Check the IP address on the IEC61850 subnetwork and change it if needed.
When the SCD file is direcly exported from PCM600, it will use the IP address of
the PCM600 computer, not the COM600.
The communication towards the 615 series devices is now ready. For information on
how to finalize the single-line diagram and enable parameter setting through COM600
HMI, see COM600 documentation.

Using the Web HMI

WHMI is enabled by default. Log in with the proper user rights to use the WHMI.
1.
To enable the WHMI, select Main menu/Configuration/HMI/Web HMI mode
via the LHMI.
2.
Reboot the IED for the change to take effect.
1MAC108982-MB A
615 series ANSI
Engineering Manual