Iec 61850 communication protocol
Hide thumbs Also See for Relion 630 Series:
Table of Contents

Advertisement

Section 3
Substation Configuration description Language (SCL)
3.4
3.4.1
22
receiver. The control services are not directly engineered. They are included in the
data objects, which handle both directions the command (control) and the response
(monitoring). When routing the DO in monitoring direction, the control is also known
by the clients.
The number of data objects and data attributes per DO is defined by the used LN type
in this IED. The content of logical node types and DO types are defined in the DTT.
This also means that the definitions in the DTT section have to be unique with an SCD
file.

Tool concept

The IEC 61850-6 defines a number of roles for tools. In the Relion
is defined as the IED tool, and IET600 is defined as the system engineering tool.
The sections in SCL contain properties that are to be configured by these tools. There
is no relation between one section and one specific tool. The task of the IED tool is to
configure all properties for the IED, while the system tool has the task to define the
place of the IED in the system and its communication dependencies. For example, the
plant structure in PCM600 results in the subsystem section in SCL regarding the
subsystem structure down to the IED level. PCM600 also configures the IED section
as a result of the IED configuration. In PCM600, the configuration properties for SCL
are handled automatically as a result of the configuration, except for the receiving of
GOOSE information that has a dependency with the system tool.
IEC 61850 Configuration tool in PCM600 can also be used for IEC 61850 engineering
instead of IET600.

IEC 61850 engineering with PCM600 and IET600

PCM600
When an IED is instantiated, its place in the plant structure creates the
corresponding structure in the substation section in SCL. The communication
facilities are also created in the communication section.
The functionality of the IED is configured by using the Application
Configuration tool in PCM600. For each function, the corresponding logical
device and logical node(s) are created in the IED section together with its type
definition in the data type template section.
The above forms the IED capabilities from a communication perspective and are
then included in the file exported from PCM600 as a SCD, ICD or CID file.
Basic IEC 61850 engineering can be done also using the IEC 61850
Configuration tool in PCM600 without file export/import with IET600.
1MRS756793 E
®
series, PCM600
630 series
Communication Protocol Manual