Figure 76:
IEC 61850: importing a SCD file
4.
In the SCL Import Options dialog box, select how to handle the file during the
import.
Click Don't import IEDs of unknown type to protect the existing IEDs in
case the SCD file does not match the original configuration in PCM600.
Click Replace unknown if it is known that the file includes additional
IEDs that are needed. The IED of type "Generic IEC 61850 IED" is used to
integrate these kinds of IEDs into the plant structure, for example.
Click Ignore PCM Object Type to update the IED object(s) in PCM600
from the IED type(s) in the SCD file, whether or not the IED type(s) in the
SCD file matches the IED object(s) in PM600.
Click Ignore Substation Section to not import the SSD file part of the
SCD file.
5.
Click Import when the file definition has been completed.
A progress view displays the importing procedure.
6.
Make connections from the sending IEDs to the receiving function blocks with
the Signal Matrix tool.
Make connections between the signals that the server is sending and the function
blocks on the receiver's side.
7.
Write the configuration to the IED.
In the Plant Structure view, select the IED, right-click and select Write to IED.
IEC 61850 communication engineering
IEC09000631-1-en.vsd
Section 7
109