1MAC108982-MB A
Section 2
615 series ANSI
Engineering Manual
IED engineering process
PCM600 is used for various tasks in the IED engineering process.
•
IED engineering management
•
Organizing the bay IEDs in the structure of the substation by defining
voltage levels and bays below the substation. PCM600 manages the project.
•
Configuring the IED functions (for example, protection and control
functions) by using the Application Configuration tool.
•
Configuring the parameters and setting values for the IED itself and for the
process functions by using the Parameter Setting tool.
•
Drawing single-line diagrams and making links to dynamic process values
by using the Graphical Display Editor. The single-line diagrams are
displayed in LHMI on the bay IED.
•
Configuring connections between the application configuration function
blocks and physical hardware input and outputs by using the Signal Matrix
tool.
•
Communication management
•
IEC 61850 station communication engineering is done with a separate tool,
for example, CCT600. PCM600 interacts with CCT600 by importing and
exporting SCL files.
•
Configuring the GOOSE receive data connections to the IED's application
configuration function blocks by using the Application Configuration tool
and the Signal Matrix tool.
•
Configuring protocol data mapping for Modbus or DNP3 with the
Communication Management tool.
•
Disturbance record management
•
Generating overviews on the available (digital fault) recordings in all
connected protection IEDs by using the Disturbance Handling tool.
•
Manually reading the recording files (in the COMTRADE format) from the
protection IEDs by using the Disturbance Handling tool or automatically by
using the PCM600 Scheduler.
•
Managing recording files with the Disturbance Handling tool.
•
Creating recording file content overview reports for fast evaluation with
assistance of the Disturbance Handling tool.
•
Service management
Section 2
IED engineering process
11