Section 4
Setting up a project
4.7
48
GUID-187F89B8-CF8B-457B-A6C2-09E3FF34E929-ANSI V1 EN
Figure 29:
Importing IED configuration
5.
Select the .pcmi file to be imported and click Open.
After importing, the IED object is created in the plant structure.
After the .pcmi file has been imported, the IP address, the name and the technical key
that corresponds to the physical IED have to be changed.

Setting the IED IP address in a project

The IED object in PCM600 must have the same IP address and subnet mask as the
front or rear port of the physical IED to which the PC is connected. The IP address of
the physical IED's rear port can be set only via LHMI, not from PCM600.
In PCM600, there are two alternatives to set the IP address of an IED object.
1MAC108982-MB A
615 series ANSI
Engineering Manual