1MAC108982-MB A
615 series ANSI
Engineering Manual
Setting up a PCM600 project
The plant structure is built according to the substation structure.
See PCM600 documentation for the recommended size of a
project. Larger projects can be divided into several PCM600 projects.
The IED is created in offline or online mode. In both cases a suitable IED
connectivity package is used. Additionally, a project template can be used for the
IED creation.
The IED objects in PCM600 are renamed uniquely according to the project
definitions.
Application configuration in the Application Configuration tool
The protection or control function is configured, for example, for a feeder, as
requested.
The configuration made in the Application Configuration tool is saved to make the
interfaces and signals available for other engineering tools within PCM600, for
example, for the Parameter Setting tool.
Parameter setting and configuration in the Parameter Setting tool
The configuration parameters of the physical IED for communication channels and
the CT and VT conversion values of the transformer module, for example, are
checked.
If needed, the setting values are checked and adjusted with the Parameter Setting
tool.
Single-line diagram configuration in the Graphical Display Editor
A single-line diagram of the switching devices in a bay is created.
Measurements are included when needed.
The dynamic elements are linked to the functions created in the Application
Configuration tool; for example, a breaker object is linked to the circuit breaker
control function.
LHMI engineering
The LED behavior is defined with Parameter Setting.
The LEDs are configured with Application Configuration.
Communication protocol engineering
Section 2
IED engineering process