1MRK 500 096-UUS B
IEC 60870-5-103 is available from optical serial port where it is possible to use serial glass fibre (ST
connector) or via RS485.
The IED supports SNTP, DNP3, IEC 60870-5-103 and IRIG-B time synchronization methods with a
time-stamping resolution of 1 ms.
The IED supports the following time synchronization methods with a timestamping resolution of 1
ms:
Ethernet communication based:
SNTP (simple network time protocol)
DNP3
With special time synchronization wiring:
IRIG-B
IEC 60870-5-103
4.4

PCM600 tool

Protection and Control IED Manager PCM600 offers all the necessary functionality to work
throughout all stages of the IED life cycle.
Planning
Engineering
Commissioning
Operation and disturbance handling
Functional analysis
With the individual tool components, you can perform different tasks and functions and control
the whole substation. PCM600 can operate with many different topologies, depending on the
customer needs.
4.4.1

Connectivity packages

A connectivity package is a software component that consists of executable code and data which
enables system tools to communicate with a protection relay. Connectivity packages are used to
create configuration structures in PCM600. The latest PCM600 and connectivity packages are
backward compatible with older protection relay versions.
A connectivity package includes all of the data which is used to describe the protection relay, for
example, it contains a list of the existing parameters, data format used, units, setting range,
access rights and visibility of the parameter. In addition, it contains code which allows software
packages that consume the connectivity package to properly communicate with the protection
650 series
Operation manual
When using PCM600 for writing to the IED, ensure that the LHMI is not in a menu
position where settings can be made. Only one active transaction, from LHMI or
PCM600, is allowed at a time.