Linking process objects

To describe a process object within an IED, it needs to be established in the application
configuration, configured when given the parameters by the Parameter Setting tool and
linked to be displayed in the HMI.
Three tools are involved in the described steps.
Application Configuration tool for programming the application function block for
the apparatus and/or measurements
Parameter Setting tool for adapting the settings and/or configuration parameters of
the application function block
Graphical Display Editor for establishing the link to update the selected data
attribute in the HMI of the application function block
The following application function blocks are used to deliver the needed information:
Switch controller (of type CSWI) for an apparatus
All configured function blocks with measurements (of type MMXU) for the
measurements
1.
Right-click the apparatus symbol and select Select Input Signal.
A list of engineered switch control application function blocks opens.
2.
Select the switch control application function block that corresponds to the
selected apparatus.
3.
Right-click the measurement symbol and select Select Input Signal.
A list of the engineered measurement application function blocks opens.
4.
Select the measurement application function block that corresponds to the
selected symbol.