1MAC108982-MB A
615 series ANSI
Engineering Manual
IEC09000630 V1 EN
Figure 75:
3.2. Configure and/or re-configure the default data sets.
3.3. Configure additional Report Control Blocks when needed for each data set
used for vertical communication.
3.4. Link the IED clients to the Report Control Blocks.
4.
Conduct horizontal communication engineering.
IEC 61850 communication engineering
IEC09000630-1-en.vsd
CCT600 data set default content
Reporting data sets can only contain data intended to be
used by clients, for example, for event handling.
The data set for GOOSE may contain signals on data
attribute level.
Up to five report clients can be configured.
Section 7
107