Profinet Interface; Diagnostics Interface; Vbg-Pn-K20-Dmd)28; Diagnostics Port Rs 232 - Pepperl+Fuchs AS-I 3.0 PROFINET Manual

Table of Contents

Advertisement

AS-i 3.0 PROFINET Gateway in Stainless Steel
Electrical connection
7.5

PROFINET interface

2
1
Connection to an Ethernet network is carried out using the one of the two RJ45
sockets on the left housing side (see section <Overview of terminals, indicators
and operating elements>).
The two sockets lead to an integrated real-time switch. They are based on MDI/
MDI-X (auto-crossover) and support 100Base-TX und 10Base-T networks in
each case with full- and half duplex (auto negotiation).
Information!
The switch will operate only if supply voltage (± PWR) is present.
LEDs in the sockets (2 per socket):
Port (green)
LED flashes green: ethernet connection active (i.e. cable plugged in).
Activity (yellow)
LED flashes yellow: transmitting/receiving active.
7.6
Diagnostics interface (only with: VBG-PN-K20-D, VBG-PN-K20-DMD-EV,
VBG-PN-K20-DMD)
The service and diagnostics interface (in conjunction with AS-i Control Tools
software) is used for communication between the PC and the unit.
7.6.1

Diagnostics port RS 232

The service and diagnostics interface is configured as a mini DIN-6 female and it
is placed at the top of the housing (see section <Overview of terminals, indicators
and operating elements>).
28
LEDs
RJ45 socket
RJ45 socket
LEDs