E-## Digital In/Out - GE AF-650 GP Programming Manual

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Parameter Descriptions

3.4 E-## Digital In/Out

Parameter group related to the Digital Inputs/Outputs, additional accel/decel ramps, pulse inputs/outputs, and encoder
input.
3.4.1 E-0# Digital Inputs
3
3
Parameters to configure the Digital Inputs/Outputs and Safe Stop functions.
Parameters for configuring the input functions for the input terminals.
The digital inputs are used for selecting various functions in the frequency converter. All digital inputs can be set to the
following functions:
Digital input function
No operation
Reset
Coast inverse
Coast and reset inverse
Quick stop inverse
DC-brake inverse
Stop inverse
Start
Latched start
Reversing
Start reversing
Enable start forward
Enable start reverse
Jog
Preset reference on
Preset ref bit 0
Preset ref bit 1
Preset ref bit 2
Freeze reference
Freeze output
Speed up
Speed down
Set-up select bit 0
Set-up select bit 1
Precise stop inverse
Precises start, stop
Catch up
Slow down
Counter input
Pulse input
Ramp bit 0
Ramp bit 1
Mains failure inverse
Latched precise start
Latched precise stop inverse
DigiPot Increase
DigiPot Decrease
DigiPot Clear
Counter A (up)
Counter A (down)
Reset Counter A
42
AF-650 GP Programming Guide
Select
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[8]
[9]
[10]
[11]
[12]
[13]
[14]
[15]
[16]
[17]
[18]
[19]
[20]
[21]
[22]
[23]
[24]
[26]
[27]
[28]
[29]
[30]
[32]
[34]
[35]
[36]
[40]
[41]
[55]
[56]
[57]
[60]
[61]
[62]
DET-618C
Terminal
All *term 27, 32, 33
All
All
All
All
All
All
All *term 18
All
All *term 19
All
All
All
All *term 29
All
All
All
All
All
All
All
All
All
All
18, 19
18, 19
All
All
29, 33
29, 33
All
All
All
18, 19
18, 19
All
All
All
29, 33
29, 33
All

Hide quick links: