Parameter Descriptions
DR-38 Logic Controller State
Range:
Function:
0
[0 - 100] View the state of the event under execution by
*
the LC controller.
DR-39 Control Card Temp.
Range:
Function:
0 °C
[0 - 100 °C] View the temperature on the control card,
*
stated in °C
DR-40 Trending Buffer Full
Option:
Function:
View whether the logging buffer is full (see parameter
group ID-1#). The logging buffer will never be full
when ID-13 Trending Mode is set to [0] Log always.
[0]
No
*
[1]
Yes
DR-48 Speed Ref. After Ramp [RPM]
Range:
0 RPM
[-30000 - 30000
This parameter specifies the
*
RPM]
reference given to the frequency
converter after the speed ramp.
DR-49 Current Fault Source
Range:
Function:
0
[0 - 8] Value indicates source of current faults including
*
short circuit, over current, and phase imbalance
(from left):
1-4 Inverter
5-8 Rectifier
0 No fault recorded
3.18.4 DR-5# Ref. & Feedb.
Parameters to view the reference and feedback status
values.
DR-50 External Reference
Range:
Function:
0
[-200 - 200] View the total reference, the sum of digital,
*
analog, preset, bus and freeze references, plus
catch-up and slow-down.
DR-51 Pulse Reference
Range:
Function:
0
[-200 - 200] View the reference value from programmed
*
digital input(s). The read-out can also reflect
the impulses from an incremental encoder.
AF-650 GP Programming Guide
Function:
DET-618C
DR-52 Feedback[Unit]
Range:
0 ReferenceFeed-
[-999999.999 -
backUnit
999999.999
*
ReferenceFeed-
backUnit]
DR-53 Digi Pot Reference
Range:
Function:
0
[-200 - 200] View the contribution of the Digital Potenti-
*
ometer to the actual reference.
DR-57 Feedback [RPM]
Range:
Function:
0 RPM
[-30000 -
Read-out parameter where the actual
*
30000 RPM]
motor RPM from the feed-back source
can be read in both closed loop and
open loop. The feed-back source is
selected by PI-00 Speed PID Feedback
Source.
Function:
View the feedback unit
resulting from the
selection of unit and
3
scaling in F-50 Reference
Range, F-51 Reference/
Feedback Unit,
F-52 Minimum Reference
and F-53 Maximum
Reference.
115
3