GE AF-650 GP Programming Manual page 38

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Parameter Descriptions
F-23 Start Speed [Hz]
Range:
Function:
0 Hz
[0 -
This parameter can be used for hoist
*
500.0 Hz]
applications (cone rotor). Set a motor start
speed. After the start signal, the output speed
leaps to set value. Set the start function in
F-25 Start Function to [3] Start speed cw, [4]
Horizontal operation or [5] Adv. Vector Control/
Flux Clockwise, and set a start delay time in
F-24 Holding Time.
F-24 Holding Time
Range:
Function:
0 s
[0 - 25.5 s] This parameter refers to the start function
*
selected in F-25 Start Function.
Enter the time delay required before
commencing acceleration.
F-25 Start Function
Option:
Function:
Select the start function during start delay.
This parameter is linked to F-24 Holding Time.
[0]
DC Hold/
Energizes motor with a DC holding current
delay time
(B-00 DC Hold Current) during the start delay
time.
[1]
DC Brake/
Energizes motor with a DC braking current
delay time
(B-01 DC Brake Current) during the start delay
time.
[2]
Coast/delay
Motor coasted during the start delay time
time
(inverter off).
*
[3]
Start speed
Only possible with Advanced Vector Control.
cw
Connect the function described in F-22 Start
Speed [RPM] and F-29 Start Current in the
start delay time.
Regardless of the value applied by the
reference signal, the output speed applies
the setting of the start speed in F-22 Start
Speed [RPM] or F-23 Start Speed [Hz] and the
output current corresponds to the setting of
the start current in F-29 Start Current. This
function is typically used in hoisting
applications without counterweight and
especially in applications with a Cone-motor,
where the start is clockwise, followed by
rotation in the reference direction.
[4]
Horizontal
Only possible with Advanced Vector Control.
operation
For obtaining the function described in
F-22 Start Speed [RPM] and F-29 Start Current
during the start delay time. The motor
rotates in the reference direction. If the
reference signal equals zero (0), F-22 Start
Speed [RPM] is ignored and the output speed
equals zero (0). The output current
AF-650 GP Programming Guide
F-25 Start Function
Option:
[5]
Adv. Vector
Control/Flux
Clockwise
[6]
Hoist Mech.
Brake Rel
[7]
Adv. Vector
Control/Flux
Counter-cw
F-26 Motor Noise (Carrier Freq)
Select the carrier frequency. Changing the switching frequency
can help to reduce acoustic noise from the motor. Default
depends on power size.
Option:
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
*
[8]
DET-618C
Function:
corresponds to the setting of the start
current in F-29 Start Current.
For the function described in F-22 Start Speed
[RPM] only. The start current is calculated
automatically. This function uses the start
speed in the start delay time only. Regardless
of the value set by the reference signal, the
output speed equals the setting of the start
speed in F-22 Start Speed [RPM]. [3] Start
speed/current clockwise and [5] Advanced
Vector Control/Flux clockwise are typically
used in hoisting applications. [4] Start speed/
current in reference direction is particularly
used in applications with counterweight and
horizontal movement.
For utilizing mechanical brake control
functions, B-24 Stop Delay to B-28 Gain Boost
Factor. This parameter is only active when
H-41 Motor Control Principle is set to [3] Flux
w/ motor feedback.
Function:
1.0 kHz
1.5 kHz
Default switching frequency for
355-1200 kW / 500-1600 HP at 690
V
2.0 kHz
Default switching frequency for
250-800 kW / 350-1200 HP at
400/460 V and 37-315 kW / 50-450
HP at 690 V
2.5 kHz
3.0 kHz
Default switching frequency for
18.5-37 kW / 25-50 HP at 240 V and
37-200 kW / 50-300 HP at 400/460
V
3.5 kHz
4.0 kHz
Default switching frequency for
5.5-15 kW / 7.5-20 HP at 240 V and
11-30 kW / 15- 40 HP at 400/460 V
5.0 kHz
Default switching frequency for
0.25-3.7 kW / 0.33-5 HP at 200 V
and 0.37-7.5 kW / 0.5-10 HP at
400/460 V
6.0 kHz
3
3
37