GE AF-650 GP Programming Manual page 52

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Parameter Descriptions
E-73 Terminal 29 Pulse Output Variable
Option:
Function:
[119] Torque % lim
E-76 Terminal X30/6 Pulse Output Variable
Select the variable for read-out on terminal X30/6.
This parameter is active when the General Purpose I/O Option
Module (OPCGPIO) is installed in the frequency converter.
Option:
[0]
No operation
*
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
[100]
Output frequency
[101]
Reference
[102]
Feedback
[103]
Motor Current
[104]
Torque rel to limit
[105]
Torq relate to rated
[106]
Power
[107]
Speed
[108]
Torque
[109]
Max Out Freq
[119]
Torque % lim
E-78 Pulse Output Max Freq #X30/6
Range:
5000 Hz
[0 - 32000 Hz]
*
3.4.6 E-8# 24 V Encoder Input
Parameters to configure the Encoder outputs.
E-80 Term 32/33 Pulses Per Revolution
Range:
Function:
1024
[1 - 4096] Set the encoder pulses per revolution on the
*
motor shaft. Read the correct value from the
encoder.
E-81 Term 32/33 Encoder Direction
Option:
Function:
NOTE
This parameter cannot be adjusted
while the motor is running.
Change the detected encoder rotation
direction without changing the wiring to
the encoder.
[0]
Clockwise
Sets channel A 90° (electrical degrees)
*
behind channel B upon clockwise rotation
of the encoder shaft.
[1]
Counter
Sets channel A 90° (electrical degrees)
clockwise
ahead of channel B upon clockwise rotation
of the encoder shaft.
AF-650 GP Programming Guide
3.4.7 E-9# Bus Controlled
Parameters to configure digital, relay and pulse train
outputs to be controlled by the serial communications.
E-90 Digital & Relay Bus Control
Range:
0
[0 - 2147483647] This parameter holds the state of the
*
Function:
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9-31
Function:
Table 3.11
E-93 Pulse Out #27 Bus Control
Range:
0 %
*
E-94 Pulse Out #27 Timeout Preset
Range:
0 %
*
E-95 Pulse Out #29 Bus Control
Range:
0 %
*
E-96 Pulse Out #29 Timeout Preset
Range:
0 %
*
DET-618C
Function:
digital outputs and relays that is
controlled by bus.
A logical '1' indicates that the output is
high or active.
A logical '0' indicates that the output is
low or inactive.
Digital Output Terminal 27
Digital Output Terminal 29
Digital Output Terminal X 30/6
Digital Output Terminal X 30/7
Relay 1 output terminal
Relay 2 output terminal
Option B Relay 1 output terminal
Option B Relay 2 output terminal
Option B Relay 3 output terminal
Reserved for future terminals
Function:
[0 - 100 %] Set the output frequency transferred to the
output terminal 27 when the terminal is
configured as [45] Bus Controlled in
E-70 Terminal 27 Pulse Output Variable.
Function:
[0 - 100 %] Set the output frequency transferred to the
output terminal 27 when the terminal is
configured as [48] Bus Ctrl Timeout in
E-70 Terminal 27 Pulse Output Variable and a
time-out is detected.
Function:
[0 - 100 %] Set the output frequency transferred to the
output terminal 29 when the terminal is
configured as [45] Bus Controlled in
E-73 Terminal 29 Pulse Output Variable.
Function:
[0 - 100 %] Set the output frequency transferred to the
output terminal 29 when the terminal is
3
3
51