K-## Keypad Set-Up - GE AF-650 GP Programming Manual

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Parameter Descriptions

3.2 K-## Keypad Set-Up

Parameter group related to the fundamental functions of
the drive, keypad buttons, configuration of the keypad
display, copy-cat features, and password protection.
3
3
3.2.1 K-0# Keypad Basic Settings
Parameters for configuring basic drives settings.
K-01 Language
Option:
[0]
English
*
[1]
Deutsch
[2]
Francais
[4]
Spanish
[5]
Italiano
[10] Chinese
[22] English US
[24] Russian
K-02 Motor Speed Unit
Option:
Function:
NOTE
This parameter cannot be adjusted while the
motor is running.
NOTE
Changing the Motor Speed Unit will reset
certain parameters to their initial value. It is
recommended to select the motor speed unit
first, before modifying other parameters.
[0]
RPM Selects display of motor speed variables and
parameters (i.e. references, feedbacks and limits) in
terms of motor speed (RPM).
[1]
Hz
Selects display of motor speed variables and
*
parameters (i.e. references, feedbacks and limits) in
terms of output frequency to the motor (Hz).
K-03 Regional Settings
Option:
[0]
Interna-
tional
[1]
US
*
24
AF-650 GP Programming Guide
Function:
Defines the language to be used in the
display. .
Function:
NOTE
This parameter cannot be adjusted while
the motor is running.
Activates P-07 Motor Power [kW] for setting the
motor power in kW and sets the default value
of F-04 Base Frequency to 50 Hz.
Activates P-07 Motor Power [kW] for setting the
motor power in HP and sets the default value
of F-04 Base Frequency to 60 Hz.
K-04 Operating State at Power-up
Option:
Function:
Selects the operating mode upon
reconnection of the frequency converter to
mains voltage after power down in Hand
(local) operation mode.
[0]
Resume
Restarts the frequency converter, maintaining
the same and the same start/stop settings
(applied by [Hand/Off]) as before the
frequency converter was powered down.
[1]
Forced stop,
Restarts the frequency converter with a saved
*
ref=old
local reference, after mains voltage reappears
and after pressing [Hand].
[2]
Forced stop,
Resets the local reference to 0 upon
ref=0
restarting the frequency converter.
3.2.2 K-1# Keypad Set-up Operations
Define and control the individual parameter setups.
The frequency converter has four parameter setups that
can be programmed independently of each other. This
makes the frequency converter very flexible and able to
solve advanced control functionality problems, often
saving the cost of external control equipment. For example
these can be used to program the frequency converter to
operate according to one control scheme in one setup
(e.g. motor 1 for horizontal movement) and another
control scheme in another setup (e.g. motor 2 for vertical
movement). Alternatively they can be used by an OEM
machine builder to identically program all their factory
fitted frequency converters for different machine types
within a range to have the same parameters and then
during production/commissioning simply select a specific
setup depending on which machine the frequency
converter is installed on.
The active setup (i.e. the setup in which the frequency
converter is currently operating) can be selected in
K-10 Active Set-up and is displayed in the keypad. Using
Multi set-up it is possible to switch between setups with
the frequency converter running or stopped, via digital
input or serial communication commands. If it is necessary
to change setups whilst running, ensure K-12 This Set-up
Linked to is programmed as required. Using K-11 Edit Set-up
it is possible to edit parameters within any of the setups
whilst continuing the frequency converter operation in its
Active Setup which can be a different setup to that being
edited. Using K-51 Set-up Copy it is possible to copy
parameter settings between the setups to enable quicker
commissioning if similar parameter settings are required in
different setups.
K-10 Active Set-up
Option:
Function:
Select the set-up to control the frequency
converter functions.
DET-618C

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents