Dn-## Devicenet Fieldbus - GE AF-650 GP Programming Manual

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Parameter Descriptions

3.11 DN-## DeviceNet Fieldbus

Parameter group related to Field Installed DeviceNet
Network Communications Option Module.
3.11.1 DN-0# Common Settings
Parameters to configure the commom settings for
DeviceNet.
DN-00 DeviceNet Protocol
Option:
Function:
[1]
DeviceNet
View the active CAN protocol.
*
NOTE
The options depend on installed option.
DN-01 Baud Rate Select
Select the network transmission speed. The selection must
correspond to the transmission speed of the master and the
other network nodes.
Option:
[16]
10 Kbps
[17]
20 Kbps
[18]
50 Kbps
[19]
100 Kbps
[20]
125 Kbps
*
[21]
250 Kbps
[22]
500 Kbps
DN-02 MAC ID
Range:
Function:
63
[0 - 63] Selection of station address. Every station
*
connected to the same network must have an
unambiguous address.
DN-05 Readout Transmit Error Counter
Range:
Function:
0
[0 - 255] View the number of CAN control transmission
*
errors since the last power-up.
DN-06 Readout Receive Error Counter
Range:
Function:
0
[0 - 255] View the number of CAN control receipt errors
*
since the last power-up.
DN-07 Readout Bus Off Counter
Range:
Function:
0
[0 - 255] View the number of Bus Off events since the last
*
power-up.
AF-650 GP Programming Guide
3.11.2 DN-1# DeviceNet
Parameters to configure the Process Data Type, Config
Write, Config Read, Warnings, and keypad control of
DeviceNet.
DN-10 Process Data Type Selection
Option:
Function:
[0]
*
[1]
[2]
[3]
DN-11 Process Data Config Write
Select the process write data for I/O Assembly Instances 101/151.
Elements [2] and [3] of this array can be selected. Elements [0]
and [1] of the array are fixed.
Option:
[0]
*
[7]
[8]
[15]
[16]
[17]
[18]
[40]
[41]
[52]
[53]
[62]
DET-618C
Function:
Select the Instance (message) for data
transmission. The Instances available are
dependent upon the setting of O-10 Control
Word Profile.
When O-10 Control Word Profile is set to [0]
[0] Drive protocol, DN-10 Process Data Type
Selection options [0] INSTANCE 100/150 and
[1] INSTANCE 101/151 are available.
When O-10 Control Word Profile is set to [5]
ODVA, DN-10 Process Data Type Selection
options [2] INSTANCE 20/70 and [3] INSTANCE
21/71 are available.
Instances 100/150 and 101/151 are GE-
specific. Instances 20/70 and 21/71 are
ODVA-specific AC Drive profiles.
For guidelines in message selection, refer to
the DeviceNet Operating Instructions.
NOTE
A change to this parameter will be
executed immediately.
INSTANCE
100/150
INSTANCE
101/151
INSTANCE
20/70
INSTANCE
21/71
None
Accel Time 1
Decel Time 1
Motor Speed High Limit [Hz]
Motor Speed Low Limit [Hz]
Motor Speed High Limit [RPM]
Motor Speed Low Limit [RPM]
Torque Limiter (Driving)
Torque Limiter (Braking)
Minimum Reference
Maximum Reference
Catch up/slow Down Value